4. Mounting procedure
Turn off the power of the programmable controller, and mount the 422BD
using the following procedure.
Remove the panel cover from the top face of the base unit.
Connect the connector provided on the 422BD to the board mounting connector
provided on the base unit.
Fix the 422BD to the base unit using the M3 self-tapping screws supplied.
Tightening torque: 0.3 to 0.6 N•m (3 to 6 kgf•cm)
Remove the cut out on the left of the panel cover using a tool such as nippers or
cutters so that the terminal block can pass through.