4. Wiring
4.1 External wiring
The input and output terminals of the CL1XY2-DT1D5S operate while
using the power supplied from the interface.
When connecting a sensor to the input terminal, use a sensor of the NPN
open collector transistor type.
The output wiring is fixed to the sink output.
I/O wiring
4.2 Connection to sensor
• When using a two-wire type sensor y When using a three-wire type sensor
Replace * in the figure with the used input No.
Notes:
*1 Bleeder resistor
When connecting a two-wire type sensor or input equipment having
parallel resistor, select a sensor or equipment whose leakage current is
1.7mA or less.
If the leakage current is more than 1.7mA, connect a bleeder resistor
obtained in the following calculation formula.
Circuit image
0.5A
0.5A
24G
DA
DB
+24V
DC DC
Y0 L
X0
+24V
24G
R
R
R
CL1XY2-DT1D5S
Isolation Flat cable
dedicated
to CC-Link/LT
Flat cable
for I/O
Internal
circuit
Bleeder resistor *1
Connected to +24 V
cable
Sensor (NPN) Sensor (NPN)
X *
24G
X *
24G
Connected to +24 V
cable
Detection
circuit
Detection
circuit
5. Specifications
5.1 General specifications
Notes:
*1 The module cannot be used in an environment pressurized above the
atmospheric pressure which can be generated around the altitude of 0 m. If the
module is used in such an environment, it may fail.
*2 The module can be used in any environment even outside the control panel as
far as the requirements of the ambient operating temperature, the ambient
operating humidity, etc. are satisfied.
*3 This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within premises. Category ΙΙ applies to equipment
Item Specification
Ambient
working
temperature
0 to 55°C (32 to 131°F)
Ambient storage
temperature
-25 to 75°C (-13 to 167°F)
Ambient
operating
humidity
5 to 95%RH: Dew condensation shall not be considered.
Ambient storage
humidity
5 to 95%RH: Dew condensation shall not be considered.
Vibration
resistance
When intermittent vibration is present
Number of times of
sweep
Frequency Acceleration Half amplitude
10 times in each of
X, Y and Z directions
(for 80 min)
10 to 57Hz − 0.075mm
57 to 150Hz 9.8m/s2 −
When continuous vibration is present
Frequency Acceleration Half amplitude
10 to 57Hz − 0.035mm
57 to 150Hz 4.9m/s2 −
Impact
resistance
147 m/s2, 3 times in each of X, Y and Z directions
Operating
atmosphere
Corrosive gas shall not be present.
Operating
altitude
2,000m(6561'8") or less(*1)
Installation
place
Inside control panel (*2)
Over-voltage
category
ΙΙ or less(*3)
Degree of
contamination
2 or less (*4)
5.3 Output specifications
5.4 Performance specifications
Item
Output method
Transistor ou
(using modu
Number of output 1 point
Isolation method Isolation with
Rated load voltage 24V DC
Operating load voltage
range
Same as mo
Max. load current 0.1A/point
Max. inrush current 0.4A/10 ms
Leakage current at OFF 0.1mA or les
Max. voltage drop at ON 1V or less (m
Response
time
OFF→ON 1.0ms or les
ON→OFF 1.0ms or les
Surge suppression Zener diode
Common wiring method 1 point/1 com
Internal protection for
outputs
Internal prot
Please conn
outside.
Item
Module
power
supply
Voltage
20.4 to 28.8V
Ripple ratio:
Current
consumption
40mA (when
(Current con
current nor t
Initial current 70mA
Max. allowable
momentary power
failure period
PS1:1ms
Number of stations
occupied
4-, 8- or 16-p
Noise durability
500Vp-p
Noise width:
(by noise sim
Withstand voltage 500V AC for
Isolation resistance
10 MΩ or mo
DC terminal
by 500V DC
Protection class IP2X
I/O part connection method Connection