資料介紹:
l
tightening the terminal, use a
mmercially available small
ewdriver having a straight form that is
widened toward the end as shown
t.
ution :
e diameter of screwdriver grip is too
all, tightening torque will not be able
e achieved. Use the following recommended screwdriver or an
ropriate replacement (grip diameter: approximately 25mm (0.98")).
Wiring of Analog Input
→ For the terminal configuration, refer to Section 1.2
ake sure to short-circuit the 'V
+' and 'I
+' terminals when current is
put. (
: input channel number)
Cautions
ke sure to short-circuit the 'V
+' and 'VI-' terminals when ch is not used.
2-core shielded twisted pair cable for the analog input lines, and
arate the analog input lines from other power lines or inductive lines.
grounding resistance should be 100Ω or less.
Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared
grounding" of the following figure.
→ For details, refer to the FX3G Series User's
Manual - Hardware Edition.
Manufacturer Model
Phoenix Contact Co., Ltd. SZS 0.4×2.5
With
straight tip
2.5mm
(0.1")
0.4mm
(0.02")
Using current
input
V +, I +, ch : represents the channel number.
*1
Terminal
block
2AD-BD
I +
V +
ch
250Ω
Using voltage
input
VI-
ch
250Ω
Grounding
Grounding 88.7kΩ
88.7kΩ
110kΩ
110kΩ
I +
V +
4. Specifications
4.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
• The number of connectable expansion boards varies depending on the main unit as
follows:
FX3G-14M
, 24M
Main units : 1 unit
FX3G-40M
, 60M
Main units : 2 units
Never stack up two or more expansion boards.
For details on the system configuration, refer to the following manual.
→ Refer to the FX3G/FX3U/FX3UC Series User's Manual - Analog Control Edition
4.2 General Specifications
The general specifications are equivalent to the PLC main unit.
For general specifications, refer to the following manuals.
→ Refer to the FX3G Series User's Manual - Hardware Edition
4.3 Performance Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric distributor.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
Model name Applicability
FX3G Series PLC Ver. 1.10 or later
Item
Specifications
Voltage input Current input
Analog
input range
0 to 10V DC
(Input resistance: 198.7kΩ)
4 to 20mA DC
(Input resistance: 250 Ω)
Maximum
absolute
input
-0.5V,+15V -2mA,+30mA
4.4 List of Special Devices
As for the details of the special devices
→ Refer to the FX3G/FX3U/ FX3UC Se
Device number
BD1 BD2
Special
auxiliary
relay
M8260 M8270
Switch
OFF:
M8261 M8271
Switch
OFF:
Special
data
register
D8260 D8270 Chann
D8261 D8271 Chann
D8264 D8274
Avera
(Settin
D8265 D8275
Avera
(Settin
D8268 D8278
Error s
b0: Ch
b1: Ch
b2: Un
b3: Un
b4: EE
b5: Av
b6: 2A
b7: 2A
b15 to
D8269 D8279 Model