For dielectric with stand voltage test and insulation resistance
each product, refer to the following manual.
→ Refer to FX3G Series User's Manual - Hardware E
*2 For common grounding, refer to section 3.3.
*3 The PLC cannot be used at a pressure higher tha
atmospheric pressure to avoid damage.
*4 Input/output extension units/blocks only
2.2 Installation location
Install the PLC in an environment conforming to the
specifications (section 2.1), installation precautions and notes.
For more details, refer to FX3G Series User's Manual - Ha
Edition.
Installation location in enclosure
Space in enclosure
Extension devices can be connected on the left and right sides
main unit of the PLC.
If you intend to add extension devices in the future, keep nec
spaces on the left and right sides.
ation
stance
Fre-
quency
(Hz)
Accele-
ration
(m/s2)
Half
ampli-
tude
(mm)
Sweep Count
for X, Y, Z: 10
times
(80 min in
each
direction)
When
installed
on DIN rail
10 to 57 - 0.035
57 to 150 4.9 -
When
installed
directly
10 to 57 - 0.075
57 to 150 9.8 -
ck
stance
147m/s2 Acceleration, Action time: 11ms, 3 times by
half-sine pulse in each direction X, Y, and Z
se
stance
By noise simulator at noise voltage of 1,000Vp-p,
noise width of 1μs, rise time of 1ns and period of 30 to
100Hz
ectric
stand
age*1
1.5kV AC for one
minute
Compliant with JEM-1021
Between each terminals*1 and
ground terminal
500V AC for one
minute
lation
stance*1
5MΩ or more by
500V DC megger
unding
Class D grounding (grounding resistance: 100Ω or
less)
system is not allowed.>*2
king
osphere
Free from corrosive or flammable gas and excessive
conductive dusts
king
ude <2000m*3
Terminal
Dielectric
strength
Insulation
resistance
n units, Input/output extension units/blocks
ween power supply
minal (AC power) and
und terminal
1.5 kV AC for
one minute
ween input terminal
Between terminal of
special adapter and
ground terminal
500V AC for
1min
5MΩ or mor
500V DC megg
Special function block Each manual
A
Configuration without extension cable